Grandview Crescent at Killcare sits on a steep bush block above Putty Beach, and it’s rated BAL 40. We’re building a bushfire sprinkler system into it: 39 heads covering every door, window, deck and the roof, a 20,000 litre concrete tank cut into the rock under a suspended slab, a diesel pump in the basement plant room, and an Embarr Argus sensor on the top roof that starts the whole thing on its own.
Currently, as of writing, the plans are drawn and the in-slab piping is in.
Nobody made the owners put it in. It wasn’t a condition of their approval. They chose it as an investment in the house, to give it the best chance it can have if a fire comes up that hill.
Below is how a system like that works, how much water it needs, what it costs and where it sits in the NSW rules. If you’re planning a home on a bush block yourself, the Dream Home Brief is where I start with every client, bushfire rating included.

What a bushfire sprinkler system does, and what it can’t
A sprinkler system is built for ember attack. Embers can arrive well before the fire front and keep coming after it passes, landing on the roof, in the gutters, on decks and against window frames. The system keeps those surfaces wet while the embers and radiant heat hit them.
The CSIRO’s bushfire best practice guide calls a sprinkler system a “last line of defence”. Research presented by Dr Alan Green to Fire Australia in 2025 found sprays haven’t been shown to stop embers getting in through gaps, and that glass already hot when the water arrives can crack. The water has to arrive early, and the gaps still have to be sealed.
BAL construction does the sealing: the rated glazing, the ember screens, the sarking and the junctions. Our guide to building to BAL FZ covers that side. A sprinkler system goes on top of a house built to its BAL and never replaces one.
How a bushfire sprinkler system works
The CSIRO guide sets a standard for each of the four parts.

Water supply
A dedicated, stored supply: a tank, sometimes a pool or a dam. The CSIRO says don’t rely on mains water. Pressure can drop when the whole street is using it, and it can fail in a fire.
The pump
The pump has to run without mains power: diesel or petrol, or electric with a backup. The CSIRO also says no exposed pumps or generators, and no system that needs refuelling to keep the water going for its minimum run. It recommends a minimum four-hour supply.
Pipework and heads
The CSIRO recommends metal pipework and heads outside. Plastic hoses and fittings will likely fail in the heat. Heads are rated by flow (litres per minute) at a pressure (kPa), and a hydraulic designer works out how many you need and where.
Detection and activation
Someone can start the pump on site, start it remotely by phone, or let a sensor start it. The CSIRO suggests considering automatic activation, so nobody has to be home.
Inside the Grandview system
Embarr designed the system, project EM-5272, over five sheets: the basement, three living levels and the roof. Every head is drawn, along with the pipe size for every run and the pump it all hangs off.
39 heads at 5 litres a minute
Each of the 39 heads puts out 5 litres a minute at 150 kPa. Running together, they need 218 litres a minute at 291 kPa at the pump. The aim was full coverage of the house with a lot of small heads, each spraying a short distance. The Fire Australia research found short sprays cut the effect of wind, and Grandview is designed for N4 wind as well as BAL 40.
Above every door and window
The design notes put a sprayer above every door and window, plus heads to cover the decks. On level three, the drawings leave the final head positions to be coordinated on site with the Heka Hood awning, so the awning doesn’t block the spray onto the glass under it.

Grandview has a lot of glass, like most homes on the Coast built for a view. Glass already hot when the water arrives can crack, so the system has to start early. The detection on the roof decides when the water arrives.
Dual spray heads on the roof
The roof gets dual spray heads fed by 25 mm stainless steel pipe, exposed on the roof and running down through it in a stainless riser. This rooftop sprinkler system is the part of the pipework that sits in the open, and it’s metal, as the CSIRO recommends.
A 20,000 litre tank cut out of the sandstone
The water comes from a 20,000 litre concrete tank under a suspended slab, sawn out of the rock at basement level beside the indoor pool. For a while it looked like two pools going in side by side, with barely room to move between them. I’ve written more about that dig in building on a sloping block, and the site diary from the week the pool was poured shows the cut.

A diesel pump in the plant room
The pump is a 50 mm diesel unit in the basement plant room, inside the house, with its own cover to cut down corrosion damage. Diesel keeps it going with the power out, and inside the house it isn’t exposed to the fire. A 50 mm strainer on the outlet catches tank debris before it reaches the heads.
The Embarr Argus on the top roof
The Argus sits on the highest roof, placed for the layout of the house and the bush around it. It watches for fire about 200 metres out (Embarr rates it to detect flames up to 250 metres away) and starts the pump on its own.
It also stops the pump once the threat moves further away. The system only sprays while there’s fire close by and doesn’t drain the tank on a fire that’s passed.
Three drawing revisions, and what we changed
Embarr issued the design for approval in May 2025 and for calculation later that month. Revision C, in July 2025, picked up our comments as the builder. The pipe inside the house changed most: revision A ran 32 mm stainless steel through the living levels, and revision C changed it to 40 mm PVC pressure pipe concealed in the structure.

How much water does a bushfire sprinkler system need?
Multiply the flow by how long you want it to run. At Grandview the flow is 218 litres a minute with every head going. My arithmetic, as a worked example and not a design figure:
- One hour at full flow: about 13,000 litres
- Two hours: about 26,000 litres
- Four hours, the CSIRO’s recommended minimum supply: about 52,000 litres
With every head running nonstop, Grandview’s 20,000 litres lasts about an hour and a half. The Argus stretches it by running the pump while the fire is close and stopping it when it isn’t. Installers set their own minimums too: Water Curtain, for example, recommends at least 22,500 litres dedicated to the sprinklers.
Size your tank with your hydraulic designer, against the flow of your design and how long you want it to spray. If your block isn’t on town water, your bushfire assessment may also call for a separate static water supply for the fire brigade. Read what yours says before you lock in the tank.
Can you run bushfire sprinklers from a pool?
You can draw from a pool, with care. Water Curtain doesn’t recommend pool water, warning that it “will corrode your roof and contaminate your water supply”. Salt or chlorinated water sprayed over a roof and into the gutters is hard on metal. Grandview’s system draws from its own tank.
Pumps and power: why we didn’t rely on the grid
Power often goes early in a bushfire, and mains pressure can drop when every house on the street is using it. A system that needs either one can fail exactly when it’s needed.
Grandview has its own water and a diesel pump inside the plant room. The options are diesel, petrol, or electric with a battery or generator behind it. Whichever you choose, it has to keep going long enough without anyone refuelling it, and it can’t sit out in the open.
Automatic or manual bushfire sprinklers?
A manual system needs someone on site, or someone with a phone and a signal, to start it. Whether anyone will be there is a question for your bushfire survival plan.
An automatic system suits a house that’s often empty, like the weekenders around Killcare, Hardys Bay and Wagstaffe, and anyone whose plan is to leave early. The house can still look after itself. Embarr also has a mode for when you’re running a barbecue, which returns the system to active after eight hours (Embarr’s description).
Water Curtain’s published price guide puts its automated system, with Embarr activation, at about double its manual roof system.
Where sprinklers sit in the rules: AS 3959, AS 5414 and NSW
Grandview is built to AS 3959 for BAL 40 whether the sprinklers run or not. The sprinkler system wasn’t required. It was the owners’ choice.
The standard for the sprinklers themselves is AS 5414:2012, Bushfire water spray systems. The Fire Australia research points out that it addresses BAL 19 only and is currently being revised. On a BAL 40 or BAL FZ house, “AS 5414 compliant” tells you less than it sounds like it does.
I wouldn’t count on a sprinkler system to change your BAL or the construction it calls for. Ask your bushfire consultant and your certifier before you design around one. Our Kalakau house at Forresters Beach is built to BAL FZ, the top rating, and its construction carries that rating on its own.
Designing it in vs adding it later
On an architectural house you don’t want surface-mounted pipes everywhere. Building the system in from the start means everything can be concealed. At Grandview it’s PVC pressure pipe inside the structure and stainless steel outside, and the pipe only comes through to the outside where it has to, or straight to a head.
Concealed pipe has to be planned before the concrete. The sprinkler piping through each slab went in before the pour, the same as every conduit and pipe in the slab deck rough-in. Add to that a plant room big enough for the pump and its cover, a tank that suits the site (ours was cut from the rock before the slab went over it), roof penetrations planned with the roofing, and heads placed around the windows and awnings. Fitting all of that to a finished house means surface pipe, new penetrations and patching.
If you’re talking to builders about a bush block, ask them how they’d handle it. It belongs on your list of questions to ask a builder.
What does a bushfire sprinkler system cost?
For a system like this, budget from about $40,000. This is an indicative figure, and every house and site is different.
Published prices give you a range to compare. Water Curtain’s price guide starts at $7,500 for a basic urban system on mains water, then $20,000 to $25,000 for a manual roof system and $40,000 to $45,000 for an automated system with Embarr activation (checked November 2026).
What moves the price:
- Water storage – a new tank, and how hard it is to place on your site
- The pump – diesel or petrol against electric with backup, and its housing
- Detection – manual, remote or automatic
- Head count – the size of the house, the glazing and the decks
- Pipework – concealed in a new build, or retrofitted
- Access – a steep block like Grandview makes every trade harder
Your side of it
Building on a bush block?
Your bushfire rating shapes the whole house, sprinklers included. Section 2 of the Dream Home Brief asks about the zoning and building constraints you already know about (bushfire, flood, heritage, easements), and section 5 asks where the money sits.
Start the Dream Home BriefTesting and maintenance
A sprinkler system can sit idle for years between fires. Our installer recommends an annual inspection in early spring, before the fire season, including the strainer that catches tank debris before it reaches the heads.
Is a bushfire sprinkler system worth it?
On a bushfire block, I think it’s always worth it. Against the cost and time it takes to build your home, it’s a small percentage, and it gives the house a better chance.
It’s worth the most when the house is already built to its BAL, the system has its own water and its own power, and it starts by itself. It’s money wasted when it relies on mains water, has plastic fittings out in the open, or goes in instead of sealing the house properly.
Plan it before the design is finished, and the pipes, the tank and the plant room become part of the house from day one.
Start here